Two ways to put a flange on an HDPE line: a flange adaptor, which has a fusion end and an integral flange face, or a stub end with a separate steel backing ring. This page lists the dimensions for both, from dn40 to dn1600, with the PN rating of each steel ring. Use it when the PE line has to bolt to a valve, a pump, a filter or a steel pipe.

dn40–dn1600size range
PN10–PN20ring ratings
2joint types
SDR 9/11/17wall series

Adaptor or stub end?

 Flange adaptorStub end + backing ring
PiecesOneTwo (spigot and ring)
Fusion endElectrofusion socket or butt fusion spigotButt fusion only
Size range we moulddn40 – dn1600dn40 – dn630
Fusion joints to install11
Ring replaceableNo – moulded inYes
Best forSpeed, fewer parts on siteLarge sizes, corrosive surroundings

Both give the same bolted joint face. The choice is about installation and spares, not about pressure capability.

Electrofusion flange adaptors

A coil socket on the PE side and a moulded flange face on the other. The welder fuses the socket, the flange is then bolted to the mating flange with a gasket. No facing machine, no backing ring, and the joint can be made in a trench where the pipe will not move.

Electrofusion Flange Adaptordn50–dn800 · 19 sizes

19 sizes, dn50 to dn800. SDR9, 11 and 17 sockets where the table shows them.

Electrofusion Flange Adapter – dn50–dn800 · 19 sizes
SizeSDR SeriesSizeSDR SeriesSizeSDR SeriesSizeSDR Series
dn5011/9dn12511dn31511/17dn56011/17
dn6311/9dn16011/9dn35511/17dn63017
dn7511/9dn20017/11/9dn40011/17dn71017
dn9011/9dn22517/11dn45011/17dn80017
dn11011/9dn25017/11/9dn50011/17  

Butt fusion flange adaptors

Plain spigot on the PE side, moulded flange face on the other. Welded like a pipe end, so the joint is full section and the fitting is the only part of the joint that can fail – which is why it is the default above dn800.

Butt Fusion Flange Adaptordn40–dn1600 · 28 sizes

28 sizes, dn40 to dn1600.

Butt Fusion Flange Adapter – dn40–dn1600 · 28 sizes
SizeSDR SeriesSizeSDR SeriesSizeSDR SeriesSizeSDR Series
dn4011dn14011/17dn31511/17dn71011/17
dn5011dn16011/17dn35511/17dn80011/17
dn6311dn18011/17dn40011/17dn90011/17
dn7511dn20011/17dn45011/17dn100011/17
dn9011/17dn22511/17dn50011/17dn120011/17
dn11011/17dn25011/17dn56011/17dn1400#17
dn12511/17dn28011/17dn63011/17dn160017

Butt Fusion Flange Steel Ringdn40–dn1200 · 26 sizes

The backing ring that goes behind a butt fusion flange face. Listed by size and PN rating; the ring is what carries the bolt load.

Butt Fusion Flange Steel Ring – dn40–dn1200 · 26 sizes
SizePN RatingSizePN RatingSizePN RatingSizePN Rating
dn4016dn14016dn31510/16dn71010/16
dn5016dn16016dn35510/16dn80010/16
dn6316dn18016dn40010/16dn90010/16
dn7516dn20010/16dn45010/16dn100010/16
dn9016dn22510/16dn50010/16dn120010/16
dn11016dn25010/16dn56010/16  
dn12516dn28010/16dn63010/16  

Stub ends

A stub end is a short spigot with a rolled flare at one end. It is butt welded to the pipe, the steel ring slides over the spigot, and tightening the bolts pulls the flare against the mating flange face. Because the PE part never carries the bolt load, the ring can be a different material – and it can be replaced.

Butt Fusion Stub Enddn40–dn630 · 18 sizes

18 sizes, dn40 to dn630, in SDR11 and SDR17.

Butt Fusion Stub End – dn40–dn630 · 18 sizes · PE100 gas series
SizeSDR11SDR17SizeSDR11SDR17
dn40✓-dn225✓✓
dn50✓-dn250✓✓
dn63✓-dn315✓✓
dn75✓✓dn355✓✓
dn90✓✓dn400✓✓
dn110✓✓dn450✓✓
dn125✓✓dn500✓✓
dn160✓✓dn560✓✓
dn200✓✓dn630✓✓

Steel backing rings

The ring is the only metal part in the joint. Its PN rating has to match the line, and its drilling has to match whatever it is bolting to. Standard rings follow the SDR of the PE: SDR17 → PN10, SDR11 → PN16, SDR9 → PN20.

Electrofusion Flange Steel Ringdn50–dn800 · 18 sizes

18 sizes, dn50 to dn800, PN10 to PN20.

Electrofusion Flange Steel Ring – dn50–dn800 · 18 sizes
SizePN RatingSizePN RatingSizePN RatingSizePN RatingSizePN Rating
dn5016/20dn11016/20dn25010/16/20dn45010dn71010
dn6316/20dn12516dn31510/16dn50010/16dn80010
dn7516/20dn16016/20dn35510/16dn56010/16  
dn9016/20dn20010/16/20dn40010/16dn63010  
Ring corrosion is the usual failure mode on an above-ground flanged joint, not the PE. Where the ring is exposed, specify a coated or galvanised ring, or switch to a stub end so the ring can be changed without cutting the line.

PE100 gas distribution series

Gas flange adaptors are moulded as a separate series for SDR11 and SDR17.

Electrofusion Flange Adaptor (gas)dn110–dn400 · 7 sizes

Electrofusion Flange Adaptor – dn110–dn400 · 7 sizes · PE100 gas series
SizeSDR11SDR17
dn110✓-
dn125✓-
dn160✓-
dn200✓-
dn250✓-
dn315✓-
dn400✓-

How to specify a flanged joint

  1. PE size and series – dn and SDR.
  2. Fusion method – electrofusion socket or butt fusion spigot.
  3. PN rating of the ring – PN10, PN16 or PN20.
  4. Mating standard and drilling – send the drawing or the bolt circle.
  5. Gasket and bolts are not part of the fitting; say if you want them quoted with it.

For a joint that has to be opened for maintenance, the stub end with a replaceable ring is the cheaper decision over the life of the line, even though the adaptor costs less on day one.

How to read these tables

  • SDR series – the wall thickness series the fitting is made for. Where two or three are listed (for example 17/11/9), the same body is moulded for each of those series.
  • dn90 × 63 – a reducing item: the main run is dn90 and the branch or outlet is dn63.
  • dn110 × 63 in a saddle table – the outlet saddle for a dn110 main with a dn63 branch.
  • Sizes are in mm and are outside diameters (OD) unless a DN figure is given for a steel end.
  • ✓ / – in the gas and valve tables: available, or not listed in that series. – means not in the standard range, not that it cannot be made – ask us.
  • * after a size – machined from the next larger butt fusion body rather than moulded. Same dimensions and same pressure rating, longer lead time.
  • # – that mould was in development when this page was published, whether the mark sits on a size or in the series column. Confirm the lead time with us before you put it in a tender.
Wall series to nominal pressure, PE100 at 20 °C water
SDR seriesSDR 17SDR 11SDR 9
Nominal pressurePN 10PN 16PN 20
Typical serviceWater distribution, gravity and low pressureGeneral pressure pipe, gas distributionHigher pressure, industrial lines

Frequently asked questions

Flange adaptor or stub end – which should I use?

A flange adaptor is one piece: the flange face is moulded onto the fusion end, so there is one fusion joint and nothing to assemble. A stub end is a short spigot with a rolled flare; a separate steel backing ring is slipped over it and pulls the flare against the mating flange. The stub end is cheaper in large sizes and lets the ring be replaced if it corrodes; the adaptor is faster to install and needs no ring inventory.

What does the PN number on the steel ring mean?

It is the nominal pressure rating of the flanged joint, and in our tables it follows the SDR of the PE: SDR17 gives PN10, SDR11 gives PN16, SDR9 gives PN20. Where a cell lists 16/20 both rings are available for that size.

Does the drilling match my existing flange?

Tell us the mating standard when you order – the ring drilling is matched to it rather than assumed. Sending the flange drawing or the bolt circle and bolt count is enough.

Can the flange adaptor be electrofusion on one side only?

Yes. The electrofusion flange adaptor has a coil socket on the PE side and a plain flange face; there is nothing to weld on the flange side, it bolts.