Two ways to put a flange on an HDPE line: a flange adaptor, which has a fusion end and an integral flange face, or a stub end with a separate steel backing ring. This page lists the dimensions for both, from dn40 to dn1600, with the PN rating of each steel ring. Use it when the PE line has to bolt to a valve, a pump, a filter or a steel pipe.
Adaptor or stub end?
| Flange adaptor | Stub end + backing ring | |
|---|---|---|
| Pieces | One | Two (spigot and ring) |
| Fusion end | Electrofusion socket or butt fusion spigot | Butt fusion only |
| Size range we mould | dn40 – dn1600 | dn40 – dn630 |
| Fusion joints to install | 1 | 1 |
| Ring replaceable | No – moulded in | Yes |
| Best for | Speed, fewer parts on site | Large sizes, corrosive surroundings |
Both give the same bolted joint face. The choice is about installation and spares, not about pressure capability.
Electrofusion flange adaptors
A coil socket on the PE side and a moulded flange face on the other. The welder fuses the socket, the flange is then bolted to the mating flange with a gasket. No facing machine, no backing ring, and the joint can be made in a trench where the pipe will not move.
Electrofusion Flange Adaptordn50–dn800 · 19 sizes
19 sizes, dn50 to dn800. SDR9, 11 and 17 sockets where the table shows them.
| Size | SDR Series | Size | SDR Series | Size | SDR Series | Size | SDR Series |
|---|---|---|---|---|---|---|---|
| dn50 | 11/9 | dn125 | 11 | dn315 | 11/17 | dn560 | 11/17 |
| dn63 | 11/9 | dn160 | 11/9 | dn355 | 11/17 | dn630 | 17 |
| dn75 | 11/9 | dn200 | 17/11/9 | dn400 | 11/17 | dn710 | 17 |
| dn90 | 11/9 | dn225 | 17/11 | dn450 | 11/17 | dn800 | 17 |
| dn110 | 11/9 | dn250 | 17/11/9 | dn500 | 11/17 |
Butt fusion flange adaptors
Plain spigot on the PE side, moulded flange face on the other. Welded like a pipe end, so the joint is full section and the fitting is the only part of the joint that can fail – which is why it is the default above dn800.
Butt Fusion Flange Adaptordn40–dn1600 · 28 sizes
28 sizes, dn40 to dn1600.
| Size | SDR Series | Size | SDR Series | Size | SDR Series | Size | SDR Series |
|---|---|---|---|---|---|---|---|
| dn40 | 11 | dn140 | 11/17 | dn315 | 11/17 | dn710 | 11/17 |
| dn50 | 11 | dn160 | 11/17 | dn355 | 11/17 | dn800 | 11/17 |
| dn63 | 11 | dn180 | 11/17 | dn400 | 11/17 | dn900 | 11/17 |
| dn75 | 11 | dn200 | 11/17 | dn450 | 11/17 | dn1000 | 11/17 |
| dn90 | 11/17 | dn225 | 11/17 | dn500 | 11/17 | dn1200 | 11/17 |
| dn110 | 11/17 | dn250 | 11/17 | dn560 | 11/17 | dn1400# | 17 |
| dn125 | 11/17 | dn280 | 11/17 | dn630 | 11/17 | dn1600 | 17 |
Butt Fusion Flange Steel Ringdn40–dn1200 · 26 sizes
The backing ring that goes behind a butt fusion flange face. Listed by size and PN rating; the ring is what carries the bolt load.
| Size | PN Rating | Size | PN Rating | Size | PN Rating | Size | PN Rating |
|---|---|---|---|---|---|---|---|
| dn40 | 16 | dn140 | 16 | dn315 | 10/16 | dn710 | 10/16 |
| dn50 | 16 | dn160 | 16 | dn355 | 10/16 | dn800 | 10/16 |
| dn63 | 16 | dn180 | 16 | dn400 | 10/16 | dn900 | 10/16 |
| dn75 | 16 | dn200 | 10/16 | dn450 | 10/16 | dn1000 | 10/16 |
| dn90 | 16 | dn225 | 10/16 | dn500 | 10/16 | dn1200 | 10/16 |
| dn110 | 16 | dn250 | 10/16 | dn560 | 10/16 | ||
| dn125 | 16 | dn280 | 10/16 | dn630 | 10/16 |
Stub ends
A stub end is a short spigot with a rolled flare at one end. It is butt welded to the pipe, the steel ring slides over the spigot, and tightening the bolts pulls the flare against the mating flange face. Because the PE part never carries the bolt load, the ring can be a different material – and it can be replaced.
Butt Fusion Stub Enddn40–dn630 · 18 sizes
18 sizes, dn40 to dn630, in SDR11 and SDR17.
| Size | SDR11 | SDR17 | Size | SDR11 | SDR17 |
|---|---|---|---|---|---|
| dn40 | ✓ | - | dn225 | ✓ | ✓ |
| dn50 | ✓ | - | dn250 | ✓ | ✓ |
| dn63 | ✓ | - | dn315 | ✓ | ✓ |
| dn75 | ✓ | ✓ | dn355 | ✓ | ✓ |
| dn90 | ✓ | ✓ | dn400 | ✓ | ✓ |
| dn110 | ✓ | ✓ | dn450 | ✓ | ✓ |
| dn125 | ✓ | ✓ | dn500 | ✓ | ✓ |
| dn160 | ✓ | ✓ | dn560 | ✓ | ✓ |
| dn200 | ✓ | ✓ | dn630 | ✓ | ✓ |
Steel backing rings
The ring is the only metal part in the joint. Its PN rating has to match the line, and its drilling has to match whatever it is bolting to. Standard rings follow the SDR of the PE: SDR17 → PN10, SDR11 → PN16, SDR9 → PN20.
Electrofusion Flange Steel Ringdn50–dn800 · 18 sizes
18 sizes, dn50 to dn800, PN10 to PN20.
| Size | PN Rating | Size | PN Rating | Size | PN Rating | Size | PN Rating | Size | PN Rating |
|---|---|---|---|---|---|---|---|---|---|
| dn50 | 16/20 | dn110 | 16/20 | dn250 | 10/16/20 | dn450 | 10 | dn710 | 10 |
| dn63 | 16/20 | dn125 | 16 | dn315 | 10/16 | dn500 | 10/16 | dn800 | 10 |
| dn75 | 16/20 | dn160 | 16/20 | dn355 | 10/16 | dn560 | 10/16 | ||
| dn90 | 16/20 | dn200 | 10/16/20 | dn400 | 10/16 | dn630 | 10 |
PE100 gas distribution series
Gas flange adaptors are moulded as a separate series for SDR11 and SDR17.
Electrofusion Flange Adaptor (gas)dn110–dn400 · 7 sizes
| Size | SDR11 | SDR17 |
|---|---|---|
| dn110 | ✓ | - |
| dn125 | ✓ | - |
| dn160 | ✓ | - |
| dn200 | ✓ | - |
| dn250 | ✓ | - |
| dn315 | ✓ | - |
| dn400 | ✓ | - |
How to specify a flanged joint
- PE size and series – dn and SDR.
- Fusion method – electrofusion socket or butt fusion spigot.
- PN rating of the ring – PN10, PN16 or PN20.
- Mating standard and drilling – send the drawing or the bolt circle.
- Gasket and bolts are not part of the fitting; say if you want them quoted with it.
For a joint that has to be opened for maintenance, the stub end with a replaceable ring is the cheaper decision over the life of the line, even though the adaptor costs less on day one.
How to read these tables
- SDR series – the wall thickness series the fitting is made for. Where two or three are listed (for example
17/11/9), the same body is moulded for each of those series. - dn90 × 63 – a reducing item: the main run is dn90 and the branch or outlet is dn63.
- dn110 × 63 in a saddle table – the outlet saddle for a dn110 main with a dn63 branch.
- Sizes are in mm and are outside diameters (OD) unless a DN figure is given for a steel end.
- ✓ / – in the gas and valve tables: available, or not listed in that series. – means not in the standard range, not that it cannot be made – ask us.
- * after a size – machined from the next larger butt fusion body rather than moulded. Same dimensions and same pressure rating, longer lead time.
- # – that mould was in development when this page was published, whether the mark sits on a size or in the series column. Confirm the lead time with us before you put it in a tender.
| SDR series | SDR 17 | SDR 11 | SDR 9 |
|---|---|---|---|
| Nominal pressure | PN 10 | PN 16 | PN 20 |
| Typical service | Water distribution, gravity and low pressure | General pressure pipe, gas distribution | Higher pressure, industrial lines |
Frequently asked questions
Flange adaptor or stub end – which should I use?
A flange adaptor is one piece: the flange face is moulded onto the fusion end, so there is one fusion joint and nothing to assemble. A stub end is a short spigot with a rolled flare; a separate steel backing ring is slipped over it and pulls the flare against the mating flange. The stub end is cheaper in large sizes and lets the ring be replaced if it corrodes; the adaptor is faster to install and needs no ring inventory.
What does the PN number on the steel ring mean?
It is the nominal pressure rating of the flanged joint, and in our tables it follows the SDR of the PE: SDR17 gives PN10, SDR11 gives PN16, SDR9 gives PN20. Where a cell lists 16/20 both rings are available for that size.
Does the drilling match my existing flange?
Tell us the mating standard when you order – the ring drilling is matched to it rather than assumed. Sending the flange drawing or the bolt circle and bolt count is enough.
Can the flange adaptor be electrofusion on one side only?
Yes. The electrofusion flange adaptor has a coil socket on the PE side and a plain flange face; there is nothing to weld on the flange side, it bolts.