PE and PVC cannot be glued to each other, and the reason is the material, not the technique. Every PE to PVC connection is mechanical. This page covers the three methods that work, the outside-diameter trap that catches most people, and what we supply on the PE side of the joint.

3methods that work
dn20–dn1600PE side range
0glue joints possible
1diameter trap

Why you cannot solvent-weld PE to PVC

PVC joints are made with solvent cement: the cement softens both surfaces and they fuse as the solvent evaporates. That works because PVC dissolves in the solvent. Polyethylene does not: it is a non-polar, semi-crystalline material with no solvent that will soften it at room temperature, which is exactly why it is chemically inert and why it is joined by melting instead.

So a PE to PVC connection is always a mechanical joint, and the question is only which mechanical joint. There are three that work, and one that does not.

What does not work: a PVC socket with PE pipe pushed into it and cemented, or a PE pipe with a PVC coupling glued on. The cement has nothing to bond to on the PE side. It may hold for a while on a low-pressure line and it will pull apart, usually at the worst moment.

Three ways that do work

PE to PVC connection methods
MethodHow it worksWhere it is usedLimits
FlangedA flange adaptor on the PE, a flange on the PVC, bolted with a gasket betweenAny size, any pressure; the standard answer above dn63Needs a flange on both sides, and both faces have to be parallel
Mechanical transition couplingA coupling with a compression or grip seal on each end, sized for one PE OD and one PVC ODRepairs, small sizes, where no flange existsSized to the exact pair of outside diameters; a gripping seal needs a clean, round pipe
ThreadedA threaded transition fused to the PE, screwed into a PVC fittingSmall sizes, pump and filter connections, dn20 to dn63Thread standard has to match, and threads are the weakest part of the joint

For anything above dn63, the flanged connection is the one to design around: it is demountable, it is inspectable, and both materials have a standard way to present a flange.

The diameter trap: PE dn is not PVC DN

This is the mistake that costs a day on site. PE pipe is designated by outside diameter: dn110 means 110 mm outside. PVC-U pressure pipe is designated by nominal diameter, which is close to the bore, not the outside. So a PE dn110 and a PVC DN100 are the same outside diameter, and a PE dn110 and a PVC DN110 are not.

PVC-U outside-diameter series to PE dn (metric series, ISO 1452 / GB/T 10002.1)
PVC-U nominalOutside diameterMatching PE dnPVC-U nominalOutside diameterMatching PE dn
DN1520 mmdn20DN100110 mmdn110
DN2025 mmdn25DN125140 mmdn140
DN2532 mmdn32DN150160 mmdn160
DN3240 mmdn40DN200200 mmdn200
DN4050 mmdn50DN250250 mmdn250
DN5063 mmdn63DN300315 mmdn315
DN6575 mmdn75DN350355 mmdn355
DN8090 mmdn90DN400400 mmdn400
This table is the metric series. Inch-series PVC (IPS, ASTM) has different outside diameters: a 4 inch IPS pipe is 114.3 mm, which matches no PE dn exactly. If the PVC is inch-series, measure the outside diameter and work from that, not from the nominal size.

Making the flanged connection

  1. Identify both outside diameters. Measure, do not infer. The PVC nominal size and the PE dn are not the same number.
  2. Put a flange on the PE. A butt fusion flange adaptor or a stub end with a backing ring, at the SDR of the PE pipe. See flange adaptor dimensions.
  3. Put a flange on the PVC. Either a solvent-welded PVC flange with a stub, or a PVC flange adaptor. Both are PVC-side products, not ours.
  4. Match the drilling. The two flanges have to have the same bolt circle and bolt count. Give us the PVC flange drawing when you order the PE side.
  5. Gasket, bolts, sequence. A full-face gasket, bolts tightened in a cross pattern to the torque for the flange material: PVC flanges deform at a much lower torque than steel ones, and over-tightening a PVC flange is a common failure.

The one thing to get right is step 4. A PE flange and a PVC flange of the "same size" can have different drillings if they come from different standards, and the joint cannot be made without an adapter flange.

What we supply, and what we do not

The PE side of a PE to PVC joint
ConnectionPE productSize rangeTable
Flanged, mid and largeButt fusion flange adaptordn40–dn1600Flange adaptor dimensions
Flanged, mid and largeButt fusion stub end + steel ringdn40–dn630Stub end vs flange adaptor
Flanged, in a trenchElectrofusion flange adaptordn50–dn800Flange adaptor dimensions
Threaded, smallThreaded transition, female or maledn20–dn63Specifications
Not oursPVC pipe, PVC flange, PVC stub, solvent cementn/aPVC supplier
  • We supply the PE side: flange adaptors dn40 to dn1600, stub ends dn40 to dn630, backing rings PN10 to PN20, and threaded transitions dn20 to dn63.
  • We do not supply PVC pipe, PVC fittings or PVC flanges. That side of the joint comes from a PVC supplier, and it has to be specified to match.
  • We can match the drilling on the backing ring or flange to a drawing you send, so the two halves bolt together.

If the connection is at a pump, a filter or a tank outlet, the alternative to a flanged joint is often a threaded one at small sizes: a threaded transition on the PE screwed into the PVC fitting. That is quicker and cheaper, and it is limited to dn63 and to the pressure a thread can hold.

Frequently asked questions

Can HDPE pipe be glued to PVC?

No. Solvent cement works by dissolving PVC, and it has no effect on polyethylene. A cemented PE to PVC joint has no bond on the PE side and will separate. The connection has to be mechanical: flanged, a transition coupling, or threaded.

What size PE flange matches a DN100 PVC pipe?

A PE dn110, because PVC-U DN100 has a 110 mm outside diameter. The nominal sizes are different numbers for the same pipe: PE is designated by outside diameter, PVC-U by nominal diameter.

Can I connect PE to inch-series PVC?

It can be done with a mechanical transition coupling sized to the actual outside diameters, but there is no exact PE dn equivalent: 4 inch IPS is 114.3 mm outside, which is between dn110 and dn125. Measure the outside diameter and specify from that.

Do you supply the PVC side of the connection?

No. Our range is PE fittings: flange adaptors, stub ends, backing rings and threaded transitions. The PVC flange or stub comes from a PVC supplier, and the two have to share a bolt drilling, which we can match to a drawing.

Is a threaded PE to PVC connection acceptable?

For small sizes at moderate pressure, yes, and it is common at pump and filter connections. Threads are the weakest part of any joint, so above dn63 or on a high-pressure line the flanged connection is the better design.