A saddle is fused onto the outside of a pipe that is already in the ground, often already live, and it can never be moved afterwards. The procedure is short but the preparation and the cooling time carry almost all of the result. This is the sequence we recommend, and the points where it goes wrong.

4things that differ from pipe fusion
6preparation checks
9steps in the cycle
1chance to get it right

Why saddle fusion is not pipe fusion

A saddle is fused to the outside of a pipe that is already in the ground and already full. That changes four things about the weld.

What is different about a saddle joint
 Pipe or fitting fusionSaddle fusion
Surfaces in contactTwo flat or cylindrical faces of the same geometryA curved saddle body against a curved pipe outside
HeatingHeater plate, or a coil inside a socketA coil moulded into the saddle body only
What holds it in positionThe machine, or the pipe stiffnessA clamp: the saddle has to be held against the pipe through the whole cycle
What the pipe is doingEmpty, usuallyOften live, and always unable to move

Because the fit between two curved surfaces is never as good as the fit inside a socket, the clamp and the surface preparation carry more of the result than they do on a pipe joint. A saddle that is not clamped down during the cycle will give a joint that looks fused and leaks at the edge.

Before the weld

Preparation for a saddle fusion
CheckWhat to doWhy
Main is round and soundInspect the area the saddle will sit on; reject dents, deep scratches and ovalityThe saddle cannot conform to a distorted pipe, and the gap becomes a leak path
Surface is cleanWipe the full contact area, then scrape the oxide layer offThe fusion surface is the pipe outside, so it has to be prepared like one
Correct model and sizeConfirm the saddle matches the main OD, and whether it is the old or the new modelThe two models have different ranges and are not interchangeable
Clamp fitsDry-fit the clamp and the saddle before the cycleA clamp that has to be forced distorts the saddle before the coil heats it
Coil and terminals undamagedLook at the coil ends; a broken terminal means the saddle is scrapThe circuit is the weld: there is no second chance once current is applied
Control box matchedThe box has to be the one the saddle's barcode or data sheet is written forA cycle from the wrong box is the wrong amount of energy

The procedure, step by step

  1. Mark the position on the main: the centre of the outlet, and the orientation. A saddle fused in the wrong place cannot be moved.
  2. Prepare the surface over the whole contact area, not just under the outlet. Scrape, then wipe clean.
  3. Dry-fit and clamp. Seat the saddle, fit the clamp, and check that the outlet points where it should.
  4. Connect the coil to the control box and confirm the cycle: barcode scan, or the parameters from the saddle data sheet.
  5. Run the cycle without interruption. Do not adjust or re-seat the saddle while current is flowing.
  6. Let it cool fully before removing the clamp. On a live main this is the step people rush, and it is the step that decides the joint.
  7. Check the melt indicator where the saddle has one: it shows that the material reached fusion temperature.
  8. Tap the main through the outlet, with the tool that matches the outlet size, and withdraw the coupon.
  9. Check the coupon: a full disc of the main wall means the hole is complete and round. A partial coupon or a torn one means the tap was not clean.
Step 6 is where a live-main job goes wrong. The clamp comes off before the joint has cooled, the saddle relaxes, and the joint that passed the visual check leaks under pressure. The cooling time is in the saddle data sheet, and it is not a suggestion.

Tapping the main

Tapping, and what each error produces
PointCorrectIf it is wrong
Tool sizeMatched to the outlet, not to the branch pipeA step in the bore that catches pigs, scrapers and swabs
Tool conditionSharp cutter, correct for PEA torn coupon and a ragged hole edge
Advance rateSteady, without forcingHeat build-up and smearing at the hole edge
CouponFull disc, kept as evidence of a complete holeNo coupon means no proof the hole is through and clean
Sealing after withdrawalTool's own seal, then the outlet is capped or connectedAn open outlet on a live main

The outlet is then fused to the branch pipe, or capped if the branch is not being made yet. On a gas main the outlet is a record item: which saddle, which cycle, which coupon.

What a good joint looks like, and what a bad one looks like

Visual signs on a saddle joint
SignMeaningAction
Melt indicator raised or clearFusion temperature was reachedProceed
Even fillet of melt around the saddle edgeMaterial melted across the whole footprintProceed
No melt visible at one edgeClamp lifted early, or the surface was not prepared thereCut out and replace; do not tap
Saddle distorted or rockedClamp was forced, or released during the cycleReplace
Burnt or discoloured material at the coilWrong cycle: too much energyReplace, and check the control box settings
Gap visible under the saddle bodyPipe out of round, or wrong saddle model for the ODReplace with the correct model, or move to a sound section of main
A saddle cannot be tested on its own. Unlike a pipe joint in a test section, a saddle is on a live main and the only test is the pressure test of the whole network, or a leak check at the outlet. That is why the preparation and the cooling time carry the whole result.

Frequently asked questions

Can a saddle be fused to a live main?

Yes, that is what it is for. Electrofusion puts no heat source outside the saddle and nothing moves, so the main can stay in service. The clamp has to be held through the cycle and the cooling time, and the tap is made after the joint has cooled.

What is the cooling time for a saddle?

It is in the saddle data sheet and it depends on the size, so it is not a single number. The practical rule is that the clamp stays on until the joint is fully cool, not until it looks solid.

Can I re-fuse a saddle that failed?

No. A saddle is consumed by the joint. The failed one is cut off, and the replacement goes on a sound section of the main, which sometimes means moving the tapping point along the pipe.

Do I have to keep the tapping coupon?

On a gas network, yes: the coupon is the evidence that the hole is complete and the wall was cut cleanly, and it is part of the record. On water it is good practice and costs nothing.

What size tapping tool do I need?

One matched to the saddle outlet, not to the branch pipe. A dn63 outlet takes a dn63 tool even if the branch reduces further downstream.