An HDPE saddle takes a branch off a main without cutting it: the saddle is fused to the outside of the pipe, then the main is tapped through it. We mould three types, a clamp that takes a branch, a bypass that keeps the main live while you tie in, and an end plug that seals an abandoned tapping hole. All the size tables are below, water and gas series separately.

84 sizeseight saddle families
dn63–dn400main size range
dn20–dn250branch sizes
SDR 11wall series

Three saddle types, and what each one is for

A saddle is a branch fitting that clamps onto the outside of a main and fuses to it. Nothing has to be cut into the main, and in the bypass version the main can stay in service. Three types cover the jobs: taking a branch, taking a branch without shutting the main down, and sealing an old branch hole. All of them are electrofusion.

Saddle types in our range
TypeWhat it doesMain sizeBranch sizeMain can stay live
Saddle clampBranches off a main into a new service or sub-main. The outlet is fused or threaded onto the branch pipe.dn63–dn400dn20–dn250No, main is tapped under pressure
Saddle bypassBranches off a main and carries the flow round a section that has to be worked on. Two outlets, so the section can be isolated.dn63–dn315dn20–dn110Yes
Saddle end plugSeals a tapping hole in a main after a branch has been abandoned, without cutting the main.dn63–dn315None, it is a plugNo
Two models, two ranges. The clamp and the bypass each exist as an old model and a new model in our mould list, and they are different products with different size ranges: the old clamp runs dn63 – dn315 and the new one dn63 – dn225. Both are current, so quote the model when you order rather than assuming the range. Both are printed below.

Branch sizes across the range: dn20, dn25, dn32, dn50, dn63, dn90, dn110, dn250. The outlet is matched to the branch pipe OD, not to the main.

Saddle clamp

The standard tapping saddle. It wraps the main, a heating coil fuses the saddle body to the outside of the pipe, and the outlet takes the branch. The main is tapped through the fused saddle with a tapping tool, so the hole is made after the saddle is sealed to the pipe, not before.

Both models are listed: the old model covers dn63 to dn315, the new model dn63 to dn225. Where a table shows a size as dn110 × 63, the main is dn110 and the branch is dn63.

Electrofusion Saddle Clamp (old model)dn63–dn315 · 9 sizes

Old model, read the branch size after the cross. Still current, and the only clamp model that reaches dn315.

Electrofusion Saddle Clamp (Old Model) – dn63–dn315 · 9 sizes
SizeSDR SeriesSizeSDR SeriesSizeSDR SeriesSizeSDR Series
dn63 × 3211dn160 × 6311dn250 × 9011dn315 × 9011
dn90 × 6311dn200 × 9011dn250 × 11011dn315 × 11011
dn110 × 6311      

Electrofusion Saddle Clamp (new model)dn63–dn225 · 9 sizes

New model, dn63 to dn225. It reaches dn20 and dn25 branch outlets that the old model does not; the old model is the one that covers dn90 and dn110 branches up to dn315.

Electrofusion Saddle Clamp (New Model) – dn63–dn225 · 9 sizes
SizeSDR SeriesSizeSDR SeriesSizeSDR Series
dn63 × 2011dn90 × 3211dn160 × 6311
dn63 × 2511dn90 × 6311dn200 × 6311
dn63 × 3211dn110 × 6311dn225 × 6311

Saddle bypass

The bypass saddle is the one that lets the main stay live. It has a bypass outlet as well as the branch outlet, so flow can be routed around a section that is being repaired or extended while the main is still carrying pressure. This is the fitting that keeps a network on supply during a tie-in.

Old model: dn63 to dn315, 10 sizes. New model: dn63 to dn225, 16 sizes, and the new model offers more branch combinations at the small end.

Electrofusion Saddle Bypass (old model)dn63–dn315 · 10 sizes

Old model, mains dn63 to dn315 with dn32 to dn110 branches.

Electrofusion Saddle Bypass (Old Model) – dn63–dn315 · 10 sizes
SizeSDR SeriesSizeSDR SeriesSizeSDR SeriesSizeSDR Series
dn63 × 3211dn125 × 6311dn250 × 9011dn315 × 11011
dn90 × 6311dn160 × 6311dn250 × 11011  
dn110 × 6311dn200 × 9011dn315 × 9011  

Electrofusion Saddle Bypass (new model)dn63–dn225 · 16 sizes

New model, the largest table in the saddle range: 16 sizes with branches from dn20 up to dn63.

Electrofusion Saddle Bypass (New Model) – dn63–dn225 · 16 sizes
SizeSDR SeriesSizeSDR SeriesSizeSDR SeriesSizeSDR Series
dn63 × 2011dn90 × 2511dn110 × 2511dn160 × 6311
dn63 × 2511dn90 × 3211dn110 × 3211dn180 × 3211
dn63 × 3211dn90 × 6311dn110 × 6311dn200 × 6311
dn90 × 2011dn110 × 2011dn125 × 3211dn225 × 6311

Saddle end plug

When a branch is abandoned, the hole it was tapped through has to be closed. A saddle end plug fuses over that hole from the outside, so the main is sealed without being cut, drained or re-routed. The alternative, cutting out the tee and welding in a spool piece, means a shutdown and two welds; the plug is one fusion.

Sizes follow the main, dn63 to dn315. It is the same body as the clamp saddle without the outlet.

Electrofusion Saddle End Plugdn63–dn315 · 7 sizes

Sized by the main, not by the hole: one plug per main size. Same body as the clamp saddle without the outlet.

Electrofusion Saddle End Plug – dn63–dn315 · 7 sizes
SizeSDR SeriesSizeSDR SeriesSizeSDR SeriesSizeSDR Series
dn6311dn11011dn20011dn31511
dn9011dn16011dn25011  

PE100 gas series

The gas saddles are a separate mould set with their own tables, which show a tick per SDR column rather than an SDR series column. The gas range goes up to dn400 on the main, wider than the water series clamp, and every size in it is SDR 11 in the tables below.

Electrofusion Saddle Clamp (gas series)dn63–dn400 · 13 sizes

Gas series. The main goes to dn400 here, further than the water series clamp, with dn32 to dn250 branches.

Electrofusion Saddle Clamp – dn63–dn400 · 13 sizes · PE100 gas series
SizeSDR11SDR17
dn63 × 32✓-
dn90 × 63✓-
dn110 × 63✓-
dn160 × 63✓-
dn200 × 63✓-
dn200 × 90✓-
dn250 × 63✓-
dn250 × 90✓-
dn250 × 110✓-
dn315 × 63✓-
dn315 × 90✓-
dn315 × 110✓-
dn400 × 250✓-

Electrofusion Saddle Bypass (gas series)dn63–dn315 · 13 sizes

Gas series bypass, mains dn63 to dn315, dn32 to dn110 branches.

Electrofusion Saddle Bypass – dn63–dn315 · 13 sizes · PE100 gas series
SizeSDR11SDR17
dn63 × 32✓-
dn90 × 50✓-
dn90 × 63✓-
dn110 × 63✓-
dn160 × 63✓-
dn200 × 63✓-
dn200 × 90✓-
dn250 × 63✓-
dn250 × 90✓-
dn250 × 110✓-
dn315 × 63✓-
dn315 × 90✓-
dn315 × 110✓-

Electrofusion Saddle End Plug (gas series)dn63–dn315 · 7 sizes

Gas series plug, dn63 to dn315 mains.

Electrofusion Saddle End Plug – dn63–dn315 · 7 sizes · PE100 gas series
SizeSDR11SDR17
dn63✓-
dn90✓-
dn110✓-
dn160✓-
dn200✓-
dn250✓-
dn315✓-

Sizing a saddle: two numbers, not one

A saddle is specified by the main it clamps and the branch it takes, and both are outside diameters. A dn160 × 63 saddle goes on a dn160 main and takes a dn63 branch. Getting one of the two wrong is the usual ordering error.

  1. Measure the main, OD, not nominal bore. If the main is old and the class is unknown, the OD plus the wall is what identifies it.
  2. Measure the branch pipe the outlet will feed. The outlet carries the branch OD, and the branch is fused to the outlet, so the outlet material has to match the branch series.
  3. Check the outlet against the tapping tool. The hole cut in the main has to match the outlet: a dn63 outlet needs a dn63 tapping tool. Mismatched tooling leaves a step in the bore that catches pigs and scrapers.
  4. State the model: old or new for the clamp and the bypass. The ranges differ and the new model stops at dn225.
  5. Say whether the main stays live. If it does, it is a bypass saddle, and the bypass outlets have to be ordered with it.
Saddle fusion is not pipe fusion. The heating is done through a coil in the saddle body against a curved surface, and the parameters are specific to the saddle, not to the pipe. Use the cycle printed on the saddle, and check the melt indicator where the saddle has one. The procedure is written up on how HDPE pipes are joined.

Ordering checklist for saddles

  • Main OD and branch OD, both in mm, plus the SDR of each.
  • Type: clamp, bypass or end plug.
  • Model for clamp and bypass: old or new. The size ranges are different.
  • Water/industrial or gas series. Separate moulds, separate tables.
  • Tapping tool, if you need one, and the outlet size it has to match.
  • Quantity per size. Saddles are ordered by the main size they sit on, which is not always the size you count in the store.

Frequently asked questions

What does dn160 × 63 mean on a saddle?

The main is dn160 outside diameter and the branch outlet is dn63. The first number is the pipe the saddle clamps onto, the second is the pipe it feeds. Both are ODs in mm.

Can I fit a saddle without shutting the main down?

With a bypass saddle, yes, that is what it is for: the bypass keeps the section supplied while the branch is tied in. With a clamp saddle the main is tapped, which is normally done under pressure with a tapping machine but is still a live operation.

What is the difference between the old and new saddle models?

They are two separate mould sets with different size ranges: the old clamp and bypass run to dn315, the new ones stop at dn225, and the new bypass offers more branch combinations at the small end. Both are available. Quote the model you need rather than the size alone.

How do I seal a branch hole after removing a service?

With a saddle end plug fused over the hole, dn63 to dn315. It avoids cutting the main and avoids a shutdown. The hole has to be clean and round, and the plug is sized by the main, not by the hole.

Do saddles come in SDR 17?

The saddle tables list SDR 11 throughout, both water and gas series. Where the main is SDR 17 the outlet still has to match the branch pipe, so tell us both series when you order.