A gravity line is loaded from the outside, so stiffness and embedment replace pressure class, and an empty pipe in wet ground floats. This page works through that inversion, then gives the positions, the checks and the families that answer it.
A drainage line is designed upside down
A pressure main is designed from the inside out: the fluid pushes, the wall resists, and the joint has to hold. A gravity drainage line is designed the other way round. The fluid barely touches the wall, the soil presses in from outside, and the joint only has to keep soil out. Almost every under-designed drainage line fails on that inversion, not on the pipe material.
Three consequences follow. The wall is chosen for ring stiffness, not pressure class, so the SDR that appears on a drainage drawing is often 17 or 26 where a water main of the same diameter would be 11. The installation is part of the structure, so the embedment around the pipe carries load and the class of that embedment is a design decision rather than a contractor's habit. And an empty PE pipe in saturated ground floats, which is a calculation nobody does on a water main because the pipe is full and heavy.
The joint behaves differently too. A gravity line needs a soil-tight joint rather than a pressure-tight one, so butt fusion is more than enough and the specification can focus on line and level. The exception is an attenuation tank, which is a storage structure and does have to be watertight, and that is where the pressure test belongs.
The range, from the gully to the outfall
The groups follow the water downhill: a lateral from a gully or a roof, the main run, a branch into it, the outfall, and the pumped connection where the fall runs out.
| Family group | Families | Size range | Size entries | What it covers |
|---|---|---|---|---|
| Main run and outfall | 7 | dn20–dn1600 | 324 | Pipe, bends, tees, reducers, end caps and flange adaptors for the collector. |
| Laterals, tie-ins and repairs | 7 | dn20–dn1400 | 245 | Couplings, bends and tees that fuse without a machine in a confined trench. |
| Branches on a laid main | 8 | dn63–dn400 | 84 | Saddles that make a lateral without cutting the main. |
| Isolation | 2 | Ø32–Ø355 | 19 | Fusion-end valves at pumps, tanks and outlet controls. |
| Pumped connection | 2 | dn25–dn355 | 53 | Steel-to-PE transitions where the fall runs out and the line becomes a rising main. |
| Chambers and tank penetrations | 3 | dn40–dn1600 | 72 | Stub ends and flange adaptors at rigid structures, where the pipe has to settle. |
Position by position, from the gully to the outfall
| Position | Fitting that goes there | Why this one |
|---|---|---|
| Gully or roof outlet, dn110 | Electrofusion coupling or a socket fusion bend | Short, cramped connection made after the pipe is already in the ground. Electrofusion needs no machine travel. |
| Lateral to the main run | Electrofusion saddle, dn63–dn400 on the main | The main is usually laid and tested first. A saddle makes the branch without cutting it, and the cut would have to be re-supported. |
| Main run, dn160–dn630 | Butt fusion pipe, bends and tees | Long runs at shallow grade. Butt fusion keeps the bore clear with no internal bead to catch sediment. |
| Change of direction on the main | Two 45° elbows, or a single 90° only where the chamber allows | A gravity line needs access at every turn for rodding. A swept turn is rodded through; a tight 90° is not. |
| Change of diameter | Butt fusion reducer, placed where the invert can be re-formed | On a gravity line the invert, not the centreline, has to line up. A concentric reducer lifts the invert by half the diameter change, so it belongs at a chamber where the benching can pick the step up. |
| Inspection chamber entry | Flange adaptor or a plain spigot into the chamber wall | The chamber is rigid and the pipe is not. A flanged or sleeved entry lets the pipe settle without loading the wall. |
| Attenuation or detention tank | Butt fusion throughout, with flange adaptors at each tank penetration | A tank stores water, so this part of the system does have to be watertight and is pressure tested. |
| Outfall | End cap for a future connection, or a flap valve where the outfall can back up | Backflow at a river outfall is normal in flood, and a flap valve is cheaper than a flooded site. |
| Pumped connection where the fall runs out | Steel-to-PE transition, then a 45° rather than a 90° | The pump is steel and the rising main is PE. The transition is the only place the two materials meet. |
| Isolation before a pump or a tank | PE ball valve with fusion ends, Ø32–Ø355 | Maintenance isolation on a line that is otherwise gravity and valveless. |
Ring stiffness, and the number that decides it: deflection
A flexible pipe does not carry the soil load by itself, it carries it by deflecting into the embedment. The design check is therefore not a stress but a deflection: the standard limit is 5 percent of the internal diameter, and it is reached or not depending on the class of the material placed around the pipe.
| Ring stiffness | Typical wall | Embedment it assumes | Where it belongs |
|---|---|---|---|
| SN 4 | SDR 26 or thinner | Granular surround, well compacted, garden or landscape loading | Landscaped areas, shallow collectors, and any run where the surface load is pedestrian. |
| SN 8 | SDR 17 | Granular surround, compacted in layers, road loading | Under car parks, yards and roads, and the default for a municipal collector. |
| SN 16 | SDR 11 | As above, with a deeper cover or heavier traffic | Deep burial, airport or port loading, and crossings under a highway. |
The table is a starting point, not a substitute for the calculation. The load on a buried flexible pipe comes from the soil column above it and from any surface load spread through the cover, and the resistance comes from the pipe stiffness plus the soil modulus at its sides. Change the embedment from compacted granular to as-dug clay and the same pipe can go from 3 percent deflection to 8 percent, which is a pipe that has lost its shape and its capacity.
This is why a drainage package is quoted with the pipe and not after it. The fittings have to match the wall of the pipe they join, and the wall is chosen by the embedment class, which is a civil decision made before anyone asks for a price.
Hydraulic capacity: why the same bore carries more
PE is smoother than concrete or clay, and on a gravity line that difference is worth more than it sounds. Manning's roughness coefficient for PE is around 0.009 to 0.010, against 0.013 to 0.015 for concrete, and capacity goes as the inverse of that number.
| Material | Manning n | Relative capacity | What it means on a scheme |
|---|---|---|---|
| Concrete | 0.013 | 1.00 | The reference case. |
| Clay | 0.013 | 1.00 | The same as concrete for capacity; the difference is joint tightness and root intrusion. |
| PE100 | 0.009 | 1.44 | About 44 percent more capacity for the same bore and slope, or the same capacity at a smaller bore or a flatter grade. |
Two cautions before that number is used to downsize a line. The roughness advantage depends on the pipe staying clean, and a line laid flat with a slack grade silts up regardless of material. And the capacity figure assumes a full bore; a gravity line normally runs part-full, where the shape of the invert and the quality of the joints matter more than the wall roughness.
Where the advantage is unambiguously real is in a replacement: a failing concrete culvert can often be relined or replaced with a PE line of smaller diameter at the same grade and still pass the design flow, which is a smaller trench, a smaller machine and a shorter road closure.
Buoyancy: the check that gets skipped
PE100 has a density around 0.955, below that of water, so an empty pipe in saturated ground floats. On a water main the pipe is full and the question does not arise; on a drainage line it is empty most of the time, and the groundwater is highest exactly when the line is newly laid and the trench is open.
| Diameter | Net uplift per metre | What it takes to hold it down |
|---|---|---|
| dn315 | about 60 kg/m | A normal granular surround and 300 mm of cover is usually enough; check where the cover is shallow. |
| dn400 | about 100 kg/m | Cover plus compaction, or a concrete surround at a shallow crossing. |
| dn500 | about 155 kg/m | A concrete anchor block at each change of direction, and at any length where the water table sits above the pipe. |
| dn630 | about 245 kg/m | Anchors or a permanent ballast, and the check should be done on the empty case rather than the full one. |
The numbers are indicative and assume a thin-walled SDR 17 pipe; a heavier wall displaces less water and floats less, but not enough to change the conclusion at dn500 and above. The practical rule is that a large-diameter line below the water table is anchored on the empty case, and the anchors are placed at the bends, which is where a floating pipe first lifts out of line.
Attenuation tanks: where a drainage line does have to be watertight
An attenuation or detention tank is a storage structure, and storage means the water has to stay in it long enough to be released at a controlled rate. That makes the tank, and everything connected to it below the design level, a watertight system with a pressure test, which is a different requirement from the soil-tight joint used on the rest of the drainage.
| Element | Requirement | How it is verified |
|---|---|---|
| Collector and lateral runs | Soil-tight | Visual joint inspection and a line and level check. No pressure test. |
| Tank body and its internal partitions | Watertight | Water fill test to the design level, held for the period the specification states. |
| Tank penetrations and inlet or outlet pipes | Watertight | Tested with the tank, which is why the connection is flanged rather than simply spigoted in. |
| Outlet control chamber | Watertight | Tested separately, because it holds the design head and is the part that decides the release rate. |
| Geotextile and surround | Neither: it is the load path | Compaction testing, which is the check that actually decides whether the pipe keeps its shape. |
The connection detail at a tank penetration is where most of the risk sits. The tank is a rigid structure and the pipe is not, and the pipe will settle while the tank does not, so the penetration has to allow movement without losing the seal. A flange adaptor with a backing ring, set in a sleeve through the wall, does that; a pipe cast directly into the concrete does not.
The families, with the size each one actually reaches
Most municipal drainage sits between dn110 and dn630. The table is here so the wall and the size can be checked against what is actually moulded, rather than assumed from a catalogue abbreviation.
| Family | Size range | Sizes | Largest entry | Where it sits in a drainage system |
|---|---|---|---|---|
| Butt Fusion Reducer | dn50–dn630 | 78 | dn630 | Stepping down where the hydraulic model allows a smaller collector |
| Butt Fusion 90° Elbow | dn20–dn1600 | 31 | dn1600 | Chamber geometry and tight changes of direction |
| Butt Fusion 45° Elbow | dn50–dn1600 | 27 | dn1600 | Swept turns that can be rodded through |
| Butt Fusion Equal Tee | dn40–dn1600 | 27 | dn1600 | Branch into a second run or a chamber |
| Butt Fusion Reducing Tee | dn50–dn1600 | 102 | dn1600 | Lateral into a smaller collector without a second reducer |
| Butt Fusion End Cap | dn20–dn1600 | 31 | dn1600 | Future connection, and the closure at a test or flush point |
| Butt Fusion Flange Adapter | dn40–dn1600 | 28 | dn1600 | The flanged end at a tank or chamber penetration |
What a drainage package has to state before it can be quoted
| What to state | Why it moves the price |
|---|---|
| Gravity or pumped, section by section | A gravity run is SN 4 or SN 8 by ring stiffness; a rising main is a pressure class. They are different walls in one package. |
| Embedment class and cover depth | Decides the stiffness, and therefore the wall, for every metre of the run. |
| Diameter schedule, and where the invert has to stay level | Decides where each reduction sits and whether a chamber can pick the step up. On a gravity line the invert governs, not the centreline. |
| Number and position of every branch and chamber | Saddles and tees are most of the fitting count, and the chamber entries are the flanged items. |
| Water table level along the route | Decides whether buoyancy anchors are needed, at dn500 and above in particular. |
| Attenuation volume and outlet control | The tank is the watertight part of the package, with its own test and its own penetrations. |
| Surface loading: road, yard, landscape | SN 8 under a road and SN 4 under a lawn are the same diameter and different money. |
Frequently asked questions
What ring stiffness does a drainage pipe need?
SN 8 is the usual default for a municipal collector under road loading, and SN 4 is enough under landscaping where the cover is adequate and the surround is granular and compacted. SN 16 is for deep burial or heavy loading. The stiffness is only half the answer: the same pipe deflects very differently in compacted granular surround and in as-dug clay.
Which standard applies to HDPE drainage pipe?
EN 12666, for non-pressure underground plastics drainage and sewerage. It is not EN 12201 or ISO 4427, which are pressure standards for water supply and say nothing about ring stiffness or embedment. A drainage specification that cites a pressure standard has usually been copied from a water main specification.
Is HDPE suitable for gravity sewer and stormwater?
Yes, and it is common for both. The advantages are the smooth bore, the fused joint that roots cannot enter, and the length of pipe that can be laid without a joint. The design work is different from a pressure line: ring stiffness, embedment class and buoyancy replace pressure class.
Does an HDPE drainage pipe float?
An empty one does. PE100 has a density of about 0.955, so a dn500 pipe in saturated ground has roughly 155 kg per metre of net uplift, and a dn630 about 245. That is why large-diameter lines below the water table are anchored on the empty case, with the anchors at the bends where a floating pipe first lifts out of line.
How much more flow does HDPE carry than concrete?
About 44 percent more for the same bore and slope, from a Manning coefficient of roughly 0.009 against 0.013 for concrete. The caution is that the advantage depends on the line staying clean, and a flat grade silts up whatever the material. Where it is unambiguously real is in replacing a failing culvert with a smaller PE line at the same grade.
How do you keep the invert level at a change of diameter?
Not with an eccentric reducer: what we mould is concentric, and a concentric reducer raises the invert by half the diameter difference, which is exactly where a flat line holds water and collects sediment. The usual solutions are to put the reduction inside a manhole where the benching can be formed to pick up the step, or to check the small step against the self-cleansing velocity before accepting it. Either way the drawing has to show where the reduction happens, not only which size it is.
Can HDPE be used for a pumped rising main in a drainage scheme?
Yes, and it usually is where the fall runs out. That section is a pressure line, so it is specified by pressure class rather than ring stiffness, and the connection to the pump is a steel-to-PE transition because the pump casing is steel.
- HDPE fittings for water supply – the pressure duty version of the same families
- HDPE fittings for landfill leachate – the buried line where the settlement detail is the design
- HDPE fittings for mining and mineral processing – slurry and tailings lines at the other end of the velocity range
- HDPE fittings for marine outfalls and aquaculture – the seaward end of the outfall, where UV and movement take over
- Butt fusion fittings – the families used on the main run, and the machine that joins them
- Electrofusion fittings – the range used for laterals, tie-ins and repairs
- Saddle sizes – branch sizes for a lateral onto an existing main
- Reducer size chart – every reducing combination, and which ones are eccentric
- ISO, EN and GB compared – EN 12666 against the pressure standards
- Container loading calculator – how many fittings fit a 20 ft or 40 ft container
- Price lists and dimension tables – the 2026 list in Excel and PDF