The HDPE Electrofusion Elbows are heat fused. The sequence below is the standard procedure for the HDPE Electrofusion Elbow 90; the welding machine manual takes precedence wherever the two differ.
Most joint failures trace back to preparation rather than to the fusion cycle, so the preparation steps carry as much weight as the timed ones.
| Size band | Wall series | Typical use |
|---|---|---|
| dn25 - dn32 | SDR11 and SDR17 | service and house connections |
| dn40 - dn50 | SDR11 and SDR17 | service and house connections |
| dn63 | SDR11 and SDR17 | service and house connections |
Before you start
Prepare the pipe before the HDPE Electrofusion Elbow 90 joint is opened: these are the checks that decide whether the fusion cycle will be worth running.
- Cut the pipe square and remove the burrs.
- Scrape the oxidation layer off the fusion zone over the full socket depth.
- Mark the insertion depth on the pipe with a marker.
- Keep the pipe ends and the units dry and clean.
- Check that the marking matches the pipe SDR.
The scrape is the step most often skipped when installing the HDPE Electrofusion Elbow 90. PE oxidises in daylight, and a joint fused through an oxide layer looks sound and still fails under sustained pressure.
Fusion procedure
- Clamp the pipe in the welding machine.
- Face both ends until they are parallel and clean.
- Match the fusion parameters to the dn size and the SDR.
- Bring the faces to temperature and hold the specified heating time.
- Remove the heater and bring the joint together inside the changeover time.
- Hold under pressure for the full cooling time before moving the pipe.
Changeover time is the window between removing the heater and the faces meeting. It is short by design, so everything needed for the next step of the HDPE Electrofusion Elbow 90 joint should be within reach before the heater comes out.
Inspection after fusion
On a HDPE Electrofusion Elbow 90 joint, check that the insertion marks are still visible at the socket edge and that the bead is continuous and even all the way round. A bead that is thin on one side means the faces were not parallel.
Common defects and causes
These are the failures that recur on hdpe electrofusion elbow 90 installations across the dn25 to dn63 range:
- Cold joint: heating time too short, or changeover time exceeded.
- Brittle bead: material overheated or contaminated.
- Offset joint: pipe not clamped square in the machine.
- Insufficient insertion: depth mark not checked before cooling.
- Contaminated fusion zone: scraping skipped or done with a dirty blade.
Specifications
The table below lists every size held for the Electrofusion Elbow and the wall series available at each size. The ladder runs dn25–dn900 - 26 sizes - in SDR 9, 11 and SDR 17.
| Size (dn) | SDR 9 | SDR 11 | SDR 17 |
|---|---|---|---|
| dn25 | ✓ | ✓ | - |
| dn32 | ✓ | ✓ | - |
| dn40 | ✓ | ✓ | - |
| dn50 | ✓ | ✓ | - |
| dn63 | ✓ | ✓ | - |
| dn75 | ✓ | ✓ | - |
| dn90 | ✓ | ✓ | - |
| dn110 | ✓ | ✓ | ✓ |
| dn125 | ✓ | ✓ | - |
| dn140 | - | ✓ | - |
| dn160 | ✓ | ✓ | ✓ |
| dn180 | - | ✓ | - |
| dn200 | ✓ | ✓ | ✓ |
| dn225 | - | ✓ | ✓ |
| dn250 | ✓ | ✓ | ✓ |
| dn280 | - | ✓ | - |
| dn315 | ✓ | ✓ | ✓ |
| dn355 | - | ✓ | - |
| dn400 | - | ✓ | - |
| dn450 | - | ✓ | - |
| dn500 | - | ✓ | - |
| dn560 | - | - | ✓ |
| dn630 | - | ✓ | ✓ |
| dn710 | - | - | ✓ |
| dn800 | - | - | ✓ |
| dn900 | - | - | ✓ |
SDR is the outside diameter divided by the wall thickness, so the same dn carries a different wall in each series. SDR 9, 11 and SDR 17 on this product; the pressure classes for PE100 in water service at 20 °C are SDR 9 = PN 20, SDR 11 = PN 16 and SDR 17 = PN 10, and they derate at higher temperatures.
Pressure class by wall series
| Wall series | Pressure class (PE100, water, 20 °C) | Where it is used |
|---|---|---|
| SDR 9 | PN 20 | the highest pressure class in the range |
| SDR 11 | PN 16 | standard pressure pipe, gas and water |
| SDR 17 | PN 10 | large bore mains and lower pressure lines |
Full size and pressure tables for every family are on the specification library, and the derating figures are on the pressure rating page.
Related pages
Other pages in the HDPE Electrofusion Elbow 90 section, each covering a different angle of the same product family:
Family data for HDPE Electrofusion Elbow 90: the elbow dimension table gives centre-to-face, laying length and wall for every DN, and the electrofusion elbow page lists the sizes, pressure classes and material grades we mould.
-
Electrofusion Elbow 90
HDPE electrofusion elbow for gas and water mains. This 45 and 90 degree elbow is moulded from virgin PE100 grade resin, letting installers redirect buried HDPE pipework through tight trench corners
-
PE100 Electrofusion Elbow
Products Description PE100 Electrofusion Elbow 01. Electrofusion 90 degree Elbow I. Basic Definitions and Structure Electrical fusion fittings for 90° turning connections in HDPE pipeline
-
90 Degree Electrofusion Elbow | HDPE Gas and Water, PE100
90 degree HDPE electrofusion elbow in PE100 for gas and water mains, dn25 to dn900, SDR11 and SDR17. Size charts for D, L1 and L, and right-angle installation detail.
-
45 Degree Electrofusion Elbow | HDPE Gas and Water, PE100
45 degree HDPE electrofusion elbow for gas and water mains. PE100, dn25 to dn900 in SDR11 and SDR17, with the full D, L1 and L size charts.
-
90 Degree Electrofusion Elbow | PE100, dn25 to dn900
90 degree HDPE electrofusion elbow in PE100, dn25 to dn900, SDR11 and SDR17. Dimension tables for D, L1 and L, plus right-angle installation detail.
-
Electrofusion Elbow
product description electrofusion elbow This high-density polyethylene (HDPE) electrically fused 90-degree elbow is made by integrating PE100-grade high-quality raw materials with built-in copper
-
Electrofusion Transition Elbow
Products Description electrofusion transition elbow is meticulously crafted from premium HDPE raw materials and is produced in strict accordance with GB/T 13663.3 and ISO 4427 standards. The inner
-
HDPE Electrofusion 45 Degree Equal Elbow
A high-density polyethylene 45 degree equal elbow with identical socket bores on both legs, so the flow keeps its full cross-section through the entire turn. Because the fitting is equal-bore, there
-
HDPE Electrofusion Elbow
45 and 90 degree electrofusion elbow for HDPE gas and water mains.