Sizing A Generator For A Butt Fusion Or Electrofusion Machine
Nov 03, 2026
Leave a message
Remote sites run fusion machines off generators, and undersized generators are the leading cause of control board failure on inverter-type electrofusion units. The machine usually starts and welds; it just does it on a supply that sags every time the heater or the pump loads up.
Two numbers decide the size: the machine's input power and the generator's continuous rating. Neither is the number printed on the sales page.
The Sizing Table
| Machine supply | Generator continuous rating |
|---|---|
| 220 V single phase fusion machine | at least 1.7 x machine rated input power |
| 380 V three phase fusion machine | at least 1.4 x machine rated input power |
| Inverter electrofusion, cold ambient | at least 2 x rated input power |
Two clarifications that matter more than the factor:
- Continuous rating, not peak. Generator marketing quotes peak kVA. A set sold as 5 kW with 4 kW continuous will not carry a 3 kW machine plus site lighting.
- The nameplate figure is input power, not welding output. A 3.5 kW electrofusion unit draws roughly 4 kVA at full output with fan and electronics, so size from the input figure.
Why AVR Is Not Optional
An inverter electrofusion machine rectifies the incoming supply and regulates output to half a volt. When generator voltage swings 15 % on load steps, the machine's input stage works much harder and the DC bus sees the swing.
The repair pattern we see: blown IGBTs, failed input rectifiers, and control boards with burnt tracks, all on sites running a conventional non-AVR generator sized right at the machine rating. Specify a generator with automatic voltage regulation and check the datasheet deviation, typically 1 % with AVR against 10 % without.
Cable Length And Voltage Drop
| Distance machine to generator | Action |
|---|---|
| 25 m or less | Standard cable size |
| 25-50 m | One size up |
| 50-100 m | Two sizes up, or relocate the generator |
| Over 100 m | Relocate: volt drop and earth loop impedance dominate |
Volt drop is not just a convenience issue. The machine compensates by drawing more current, which raises cable temperature, softens the connector and shortens its life. A connector that has been running hot reads as intermittent open circuit within a season.
The Formula Behind The Numbers
Generator sizing
Generator kVA at least (machine input kW / power factor) x safety factor.
For a 3.5 kW machine at 0.8 power factor with a 1.7 factor: 3.5 / 0.8 x 1.7, about 7.4 kVA. That is why a 5 kVA set works until the ambient is 40 °C and the fan is at full speed, and then trips.
Site Checklist Before The First Joint
- Generator rated for the machine plus site loads: lights, grinder, phone chargers
- AVR confirmed on the data plate, not on the invoice
- Earth connection made and checked
- Cable sized per the table, connectors tight
- Input voltage measured while welding, not at idle
- Machine set to the correct supply voltage tap if it has one
If the machine already trips on start-up, work through electrofusion machine faults before blaming the generator; the two causes look identical from the display.
Frequently Asked Questions
Can I run a 3.5 kW electrofusion machine on a 5 kW generator?
Marginally, and not reliably in heat or at altitude. Use 7-8 kVA continuous with AVR.
Does a bigger generator damage the machine?
No. Generators do not push current, the machine draws what it needs. Oversizing costs fuel and capital, not safety.
Why does my machine reset when the pump starts?
Shared supply with a hydraulic pump or compressor. The voltage dip triggers undervoltage protection. Separate the feeds or increase generator capacity.
Fusion units with regulated output, correct input taps and control boards specified for generator supply, from 3.5 kW to 12 kW.